mlsanityData to 14 Oct 2026

The Hidden Water Geography of U.S. Hyperscale Data Centers in the AI Era

arXiv 2607.02531 ↗First posted 5 Jun 2026cs.CY cs.AIcited by 0

Not on the map. Why?

Abstract (arXiv)

Water use by data centers is routinely reported as a single footprint, but water is consumed through two physically distinct pathways: at the site for cooling and in the power system that generates electricity. We mapped both pathways for 472 U.S. hyperscale facilities by linking facility locations to electricity regions, hydrologic basins, and water-stress data. Under baseline assumptions, operational water consumption totals approximately 300 GL yr^-1 (range 205-451 across scenarios), with electricity-related water contributing three-quarters of the total. The two pathways produce different hotspot geographies: direct cooling burdens concentrate in stressed western and south-central basins, whereas electricity-related burdens concentrate in a few eastern grid regions with fossil-heavy supply. Just 3 of 24 hosting balancing authorities account for 59% of electricity-related water. Separating pathways identifies which decisions matter where: cooling design and water sourcing locally, electricity planning and procurement regionally

Key facts. No citing papers in the map yet (data through 14 Oct 2026). Builds on 1 of its 17 references that are in the map. First posted on arXiv 5 Jun 2026.

Builds on

1 of 17 references.

References · 1

  1. 2026Assessing the Carbon Emissions and Energy Consumption of U.S. Hyperscale Data Centerscited by 1

Built on by

Not cited yet.