Latency-Aware Deep Learning Benchmark for Real-Time Cyber-Physical Attack and Fault Classification in Inverter-Dominated Power Grids
Not on the map. Why?
Abstract (arXiv)
This work introduces a latency-aware benchmarking framework for evaluating deep learning models in power system anomaly detection using high-fidelity, time-domain signals generated from an industry-grade electromagnetic transient simulator. Eight neural network architectures, ranging from MLPs to Transformers, were systematically evaluated on streaming datasets representing both physical faults and cyber-attacks in inverter-dominated networks. All models successfully classified two representative multi-event sequences in real time with sub-cycle response times below 15 ms. However, although classification decisions occurred within one cycle, the end-to-end inference latency consistently exceeded three cycles, ranging from 50 to 90 ms. These results highlight a critical gap between algorithmic capability and protection-grade deployment, pointing to the need for further optimization and hardware acceleration. The findings establish a reproducible benchmark for sub-cycle anomaly detection and provide guidance for transitioning machine learning methods from research prototypes to real-world protection applications.
Key facts. Cited by 2 papers in the map (data through 7 Oct 2026). Builds on 1 of its 10 references that are in the map. First posted on arXiv 17 May 2026.
Builds on
1 of 10 references.
References · 1
Built on by
Citing papers per year: 2026: 2.
2 papers.