The gray-box modeling approach, which uses a semi-physical thermal network model, has been widely used in building prediction applications, such as model predictive control (MPC). However, unmeasured disturbances, such as occupants, lighting, and in/exfiltration loads, make it challenging to apply this approach to practical buildings. In this study, we propose a hybrid modeling approach that integrates the gray-box model with a model for unmeasured disturbance. After reviewing several system identification approaches, we systematically designed the unmeasured disturbance model with a model selection process based on statistical tests to make it robust. We generated data based on the building model calibrated by real operational data and then trained the hybrid model for two different weather conditions. The Hybrid model approach demonstrates the reduction of RMSE approximately 0.2-0.9C and 0.3-2C on 1-day ahead temperature prediction compared to the Conventional approach for mild (Berkeley, CA) and cold (Chicago, IL) climates, respectively. In addition, this approach was applied for experimental data obtained from the laboratory building to be used for the MPC application, showing superior prediction performances.
Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). First posted on arXiv 5 Dec 2025.
Builds on
No reference list yet.
Built on by
Citing papers per year: 2026: 1.