mlsanityData to 14 Oct 2026

Enhancing Data Center Low-Voltage Ride-Through

arXiv 2510.03867 ↗First posted 4 Oct 2025eess.SY cs.SYcited by 2

Not on the map. Why?

Abstract (arXiv)

Data center loads have expanded significantly in recent years. Compared to traditional loads, data centers are highly sensitive to voltage deviations and thus their protection mechanisms trip more proactively during voltage fluctuations. During a grid fault, simultaneous tripping of large-scale data centers can further destabilize the transmission system and even lead to cascading failures. In response, transmission system operators are imposing voltage ride-through (VRT) requirements for data centers. In this work, we enhance the VRT capability of data centers by designing voltage controllers for their internal power distribution network. We first systematically analyze VRT standards and the controllable resources related to data centers. These resources enable the design of voltage control strategies to regulate voltages internal to the data center, thereby allowing loads to remain online during voltage disturbances from the external transmission grid. We study and contrast both centralized and decentralized controllers that unify the control of heterogeneous flexible resources. Additionally, we construct an integrated test system that simulates both the transient fault response of the transmission system and the data center distribution network. Case studies demonstrate that the proposed voltage control mechanisms provide effective yet simple solutions to enhance data center low-voltage ride-through capability.

Key facts. Cited by 2 papers in the map (data through 14 Oct 2026). First posted on arXiv 4 Oct 2025.

Builds on

No reference list yet.

Built on by

Cited by year (2026 to 14 Oct)

Citing papers per year: 2026: 2.

2 papers.