mlsanityData to 14 Oct 2026

An EMD-based Method for the Detection of Power Transformer Faults with a Hierarchical Ensemble Classifier

arXiv 2110.11451 ↗First posted 21 Oct 2021cs.LG eess.SP stat.COcited by 1

Not on the map. Why?

Abstract (arXiv)

In this paper, an Empirical Mode Decomposition-based method is proposed for the detection of transformer faults from Dissolve gas analysis (DGA) data. Ratio-based DGA parameters are ranked using their skewness. Optimal sets of intrinsic mode function coefficients are obtained from the ranked DGA parameters. A Hierarchical classification scheme employing XGBoost is presented for classifying the features to identify six different categories of transformer faults. Performance of the Proposed Method is studied for publicly available DGA data of 377 transformers. It is shown that the proposed method can yield more than 90% sensitivity and accuracy in the detection of transformer faults, a superior performance as compared to conventional methods as well as several existing machine learning-based techniques.

Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). Builds on 0 of its 17 references that are in the map. First posted on arXiv 21 Oct 2021.

Builds on

0 of 17 references.

No references here yet.

Built on by

Cited by year

Citing papers per year: 2025: 1.

1 paper.