mlsanityData to 14 Oct 2026

Guaranteed Phase & Topology Identification in Three Phase Distribution Grids

arXiv 2008.01255 ↗First posted 4 Aug 2020eess.SY cs.SY math.OCcited by 1

Not on the map. Why?

Abstract (arXiv)

We present a method for joint phase identification and topology recovery in unbalanced three phase radial networks using only voltage measurements. By recovering phases and topology jointly, we utilize all three phase voltage measurements and can handle networks where some buses have a subset of three phases. Our method is theoretically justified by a novel linearized formulation of unbalanced three phase power flow and makes precisely defined and reasonable assumptions on line impedances and load statistics. We validate our method on three IEEE test networks simulated under realistic conditions in OpenDSS, comparing our performance to the state of the art. In addition to providing a new method for phase and topology recovery, our intuitively structured linearized model will provide a foundation for future work in this and other applications.

Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). First posted on arXiv 4 Aug 2020.

Builds on

No reference list yet.

Built on by

Cited by year

Citing papers per year: 2022: 1.

1 paper.