Fast Grid Splitting Detection for N-1 Contingency Analysis by Graph Computing
Not on the map. Why?
Abstract (arXiv)
In this study, a graph-computing based grid splitting detection algorithm is proposed for contingency analysis in a graph-based EMS (Energy Management System). The graph model of a power system is established by storing its bus-branch information into the corresponding vertex objects and edge objects of the graph database. Numerical comparison to an up-to-date serial computing algorithm is also investigated. Online tests on a real power system of China State Grid with 2752 buses and 3290 branches show that a 6 times speedup can be achieved, which lays a good foundation for advanced contingency analysis.
Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). First posted on arXiv 7 Apr 2019.
Builds on
No reference list yet.
Built on by
Citing papers per year: 2022: 1.