On the round-trip efficiency of an HVAC-based virtual battery
Not on the map. Why?
Abstract (arXiv)
Flexible loads, especially heating, ventilation, and air-conditioning (HVAC) systems can be used to provide a battery-like service to the power grid by varying their demand up and down over a baseline. Recent work has reported that providing virtual energy storage with HVAC systems lead to a net loss of energy, akin to a low round-trip efficiency (RTE) of a battery. In this work we rigorously analyze the RTE of a virtual battery through a simplified physics-based model. We show that the low RTEs reported in recent experimental and simulation work are an artifact of the experimental/simulation setup. When the HVAC system is repeatedly used as a virtual battery, the asymptotic RTE is 1. Robustness of the result to assumptions made in the analysis is illustrated through a simulation case study.
Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). First posted on arXiv 7 Mar 2018.
Builds on
No reference list yet.
Built on by
Citing papers per year: 2025: 1.
1 paper.