Variable Transmission Voltage for Loss Minimization in Long Offshore Wind Farm AC Export Cables
Not on the map. Why?
Abstract (arXiv)
Connection of offshore wind farms to shore requires the use of submarine cables. In the case of long HVAC connections, the capacitive charging currents limit the transfer capability and lead to high losses. This paper shows that the losses can be substantially reduced by continuously adjusting the cable operating voltage according to the instantaneous wind farm power production.Calculations for a 320 MW windfarm connected to shore via a 200 km cable at 220 kV nominal voltage shows that an annual loss reduction of 9 percent is achievable by simply using a 15 percent tap changer voltage regulation on the two transformers. Allowing a larger voltage regulation range leads to further loss reduction (13 percent for 0.4-1.0 p.u. voltage range). If the windfarm has a low utilization factor, the loss reduction potential is demonstrated to be as high as 21 percent . The methodology can be applied without introducing new technology that needs to be developed or qualified.
Key facts. Cited by 1 paper in the map (data through 14 Oct 2026). First posted on arXiv 9 Feb 2016.
Builds on
No reference list yet.
Built on by
Citing papers per year: 2023: 1.
1 paper.