mlsanityData to 14 Oct 2026

Vulnerability Analysis and Consequences of False Data Injection Attack on Power System State Estimation

arXiv 1506.03774 ↗First posted 11 Jun 2015eess.SY cs.CR cs.SYcited by 2

Not on the map. Why?

Abstract (arXiv)

An unobservable false data injection (FDI) attack on AC state estimation (SE) is introduced and its consequences on the physical system are studied. With a focus on understanding the physical consequences of FDI attacks, a bi-level optimization problem is introduced whose objective is to maximize the physical line flows subsequent to an FDI attack on DC SE. The maximization is subject to constraints on both attacker resources (size of attack) and attack detection (limiting load shifts) as well as those required by DC optimal power flow (OPF) following SE. The resulting attacks are tested on a more realistic non-linear system model using AC state estimation and ACOPF, and it is shown that, with an appropriately chosen sub-network, the attacker can overload transmission lines with moderate shifts of load.

Key facts. Cited by 2 papers in the map (data through 14 Oct 2026). First posted on arXiv 11 Jun 2015.

Builds on

No reference list yet.

Built on by

Cited by year

Citing papers per year: 2022: 1; 2023: 0; 2024: 0; 2025: 1.

2 papers.