mlsanityData to 14 Oct 2026

Impacts of Bad Data on the PMU based Line Outage Detection

arXiv 1502.04236 ↗First posted 14 Feb 2015cs.CR cs.SY eess.SYcited by 5

Not on the map. Why?

Abstract (arXiv)

Power systems become more prone to cyber-attacks due to the high integration of information technologies. In this paper, we demonstrate that the outages of some lines can be masked by injecting false data into a set of measurements. The success of the topology attack can be guaranteed by making that: 1)the injected false data obeys KCL and KVL to avoid being detected by the bad data detection program in the state estimation; 2)the residual is increased such that the line outage cannot be detected by PMU data. A quadratic programming problem is set up to determine the optimal attack vector that can maximize the residual of the outaged line. The IEEE 39-bus system is used to demonstrate the masking scheme.

Key facts. Cited by 5 papers in the map (data through 14 Oct 2026). First posted on arXiv 14 Feb 2015.

Builds on

No reference list yet.

Built on by

Cited by year

Citing papers per year: 2021: 1; 2022: 1; 2023: 0; 2024: 2; 2025: 1.

5 papers.